The gas combination valve is specially developed for commercial heating boiler, condensing boiler and premix burner. Products are widely used in hotels, schools, hospitals, government institutions, regional distributed heating gas boilers.
Combination Gas Valves TGV725
The gas combination valve is specially developed for commercial heating boiler, condensing boiler and premix burner. Products are widely used in hotels, schools, hospitals, government institutions, regional distributed heating gas boilers.
Use
• 2 shutoff valves
• Servo pressure regulator
• Inlet/outlet pressure test points
• All adjustments are accessible from the top of valve
• A fine-mesh screen is integrated at the inlet side
• Compact design suitable for installation in small modern boilers and heaters
• Specially designed for gas appliance with DBI system to light the main burner
• Servo pressure regulator ensures stable outlet pressure
• Pressure feedback ensures constant burner pressure
• Pressure switch to prevent tempering under low pressure.
• Main gas flow throttle valve regulates gas / air 1:1
Warning notes
To avoid injury to persons, damage to property or the environment, following warning notes must be observed!
Do not open, interfere with or modify the valve!
• All activities (mounting, installation, service work, etc.) must be performed by qualified staff
• Before performing any wiring changes in the connection area of the EBR…, completely isolate the unit from the main supply (all-polar disconnection)
• Ensure protection against electric shock hazard by providing adequate protection for the connection terminals.
• Check to ensure that wiring is in an orderly state
• Fall or shock can adversely affect the safety functions. Such valves must not be put into operation even if the unit does not exhibit any damage
Mounting notes
The parallel displacement regulator regulates the air/gas ratio
• Check the inlet and outlet pressure using the pressure test points provided
• Remove the protective cap
• turn the screw (white) clockwise to increase the outlet pressure
• turn the screw (white) counterclockwise to decrease the outlet pressure
• Ensure that the outlet pressure is correctly adjusted before replacing the protective cap
Regulate the main gas flow throttle valve
• turn the screw counterclockwise (yellow) to increase outlet flow
• turn the screw (white) clockwise to decrease the outlet flow
Installation notes
Main gas connection
• To prevent distortion and/or damage of the external thread, take carenot to tighten the pipe fitting too far
• Ensure that the gasket is properly placed in the right position
• Ensure that the gas flow is in the same direction as the arrow on the valve body
Pressure test points
• The valve is provided with an inlet and outlet pressure test point
• When checking the pressure, undo the screw one half turn and slip the tube over the nipple
Note
Make sure the screw is retightened after making the test.
Electrical connections
Warning
Switch off power supply before making the electrical connections. Wiring must be in accordance with local regulations. Follow the instructions supplied by themanufacture.
• Install power in accordance with the required pin connection (refer to Function)
• When making connections to the terminals of the valve, use wires and connectors which are suited for temperature up to 105℃
Checkout and Installation
• After each adjustment, put the control into operation, run it
• through several complete cycles and check to ensure that all
• burner components function correctly
Technical data
General unit data
Models
TGV725
Mounting position
Installation at any angle
Type of gas
LNG、LPG
Gas inlet pressure
Max100mba
Working voltage
220VAC,50/60H
Operating voltage tolerance
gas valve operates correctly between 85% and 110% of the rated voltage
Cut off valve rated power
44W
Cut off valve start rated current
100mA
Coil insulation grade
class F
Degree of protection
IP40
Inlet filter
no60 fine mesh
Operating temperature environment
-15-60℃
Regulating ability
Min 0.31m3/h air
Outlet pressure range for modulating
1-15 mbar
Valve class
-1st safety shutoff valve
-2nd safety shutoff valve
EN126
class A
class A
Class of regulator
class C EN88
Closing time of safety shutoff valves
within 1S
The temperature rise of the coil
△T≤75℃
Control pressure connection mode
4mm outer diameter trachea
Weight
approx. 4600g
Technical data
Environmental conditions
storage
Climate condition
Mechanical condition
temperature range
humidity
DIN EN 60 721-3-1
1K3
1M2
-30...+70℃
<95% r.h.
transport
Climate condition
Mechanical condition
temperature range
humidity
DIN EN 60 721-3-2
2K2
2M2
-15...+60℃
<95% r.h.
operation
Climate condition
Mechanical condition
temperature range
humidity
DIN EN 60 721-3-3
3K5
3M2
0...+60℃
-15...+60℃
<95% r.h.
Condensate and ice water are not allowed to enter valves.
Function
Pin connection
Note:
The coils for safety shutoff function of EBR... gas valve are DC type
Function
Cutaway view
Legend
1 1st shutoff valve(class A)
2 valve body
3 Proportional component
4 Throttle hole
5 ratio control
6 Limit screw
7 2nd shutoff valve(class A)
8 Gas / air conditioner
Dimension
In millimeters